6 Option Related Drive Parameters
YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual
25
bUS Error Auto Reset
0: Disabled
1: Enabled
0
F7-01
to
F7-04
IP Address
Sets static IP address of the SI-EP3 option when parameter
F7-13=0.
Note: Parameter F7-01 sets the most significant octet.
192 168 1 20
F7-05
to
F7-08
Subnet Mask
Sets static Subnet Mask of network connection.
Note: Parameter F7-05 sets the most significant octet
255 255 255 0
F7-09
to
F7-12
Gateway Address
Sets static Gateway address of network connection.
Note: Parameter F7-09 sets the most significant octet.
192 168 1 1
F7-13
Address Mode at
Startup
Selects how the option address is set.
0: Static
2: DCP
2
F7-14
Duplex Mode Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half (port 1)/Auto (port 2)
4: Half (port 1)/Full (port 2)
5: Auto (port 1)/Half (port 2)
6: Auto (port 1)/Full (port 2)
7: Full (port 1)/Half (port 2)
8: Full (port 1)/Auto (port 2)
1
F7-15
Communication Speed
Selection
Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
101: 10 (port 1)/100 Mbps (port 2)
102: 100 (port 1)/10 Mbps (port 2)
Default: 10
Range: 10;
100 to 102
Communication Loss
Timeout
Sets the timeout value for communication loss detection in
tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0.0 s
Min.: 0.0 s
Max.: 30.0 s
F7-23
to
F7-27
Dynamic Output
Assembly
Parameters
(SI-EP3 Firmware
Version VST800250)
Configurable outputs 1 to 5.
If a value other than 0 is assigned to parameters F7-23 to
F7-27 and F7-33 to F7-37 by the drive, that value will take
precedent over a value set by the configuration software.
If the value in the drive is 0 (default), the value from the
configuration software will be used.
0
Dynamic Output
Assembly
Parameters
(SI-EP3 Firmware
Version VST800251)
Configurable outputs 1 to 5.
If a value other than 0 is assigned in the configuration
software, those values will be used, otherwise, the values of
the drive parameters set in parameters F7-23 to F7-27 and
F7-33 to F7-37 will be used.
No.
Name
Description
Default