beautypg.com

8 troubleshooting, Drive-side error codes, 8troubleshooting – Yaskawa SI-EP3 PROFINET Installation User Manual

Page 43

background image

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

43

8 Troubleshooting

8

Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and

corrective actions are listed in

Table 10

. For additional error codes that may appear on the

drive digital operator, refer to the drive Technical Manual.

Faults

Both bUS (SI-EP3 option communication error) and EF0 (External fault input from the

SI-EP3 option) can appear as an alarm or as a fault. When a fault occurs, the digital operator

ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to

help remedy the fault:

• Is the option properly installed?

• Is the communication line properly connected to the option? Is it loose?

• Is the controller program working? Has the controller/PLC CPU stopped?

• Did a momentary power loss interrupt communications?

Table 10 Fault Display and Possible Solutions

LED Operator Display

Fault Name

bUS

Option Communication Error.
After establishing initial communication, the connection was lost
Only detected when the run command or frequency reference is assigned to
the option
(b1-01 = 3 or b1-02 = 3)

Cause

Possible Solution

Master controller (PLC) has stopped
communicating

Check that power is supplied to the PLC
Check that PLC is not in program mode

Communication cable is not connected
properly

Check for faulty wiring
Correct any wiring problems

A data error occurred due to noise

Check the various options available to minimize the effects of noise
Counteract noise in the control circuit, main circuit, and ground wiring
If a magnetic contactor is identified as a source of noise, install a surge
absorber to the contactor coil
Make sure the cable used meets the PROFINET requirements
Make sure the option ground wire is connected between option FE terminal
and the drive ground terminal connected to earth ground

Option is damaged

If there are no problems with the wiring and the error continues to occur,
replace the option.

This manual is related to the following products: