12 MECHATROLINK-III Network Topologies

YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7

21

12

MECHATROLINK-III Network Topologies

You can connect the MP3300iec Series Controller and drives or I/O with cascaded connections, star connections, or
mixed cascaded/star network topologies. The following figures show examples of these types of network topologies.

‹

Cascaded Connection

Cascaded connections allow you to connect one or more series of slave stations from the CPU Unit MECHATROLINK-
III ports. Regardless of whether a single MECHATROLINK-III port is used, as shown in

Figure 9

, or two CPU Unit

MECHATROLINK-III ports are used, as shown in

Figure 10

, these are called cascaded connections.

Figure 9

Figure 9 Cascaded Connections Using Only One Port

Figure 10

Figure 10 Cascaded Connections Using Two Ports

Note: 1. Do not connect more than 32 stations up to the final slave station to any one CPU Unit port.

2. The maximum number of stations that you can connect with cascaded connections depends on the communications cycle.

CPU Unit

No terminating resistor is required.

Up to 32 stations, including Servos and I/O

CPU Unit

No terminating

resistor is required.

Up to 62 stations, including I/O

Up to 32 Servo stations

No terminating
resistor is
required.