6 Installation and Usage Conditions

14

YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7

‹

Control Panel Cooling Method

The components that are used in the Machine Controller require the ambient operating temperature to be between 0 and
60 °C. Use one of the methods described below to ensure adequate cooling in the control panel.

NOTICE: Equipment Damage. Use forced-air cooling if the ambient temperature exceeds 55°C.

„

Control Panels with Natural Cooling

• Do not mount the Machine Controller at the top of the control panel, where the hot air that is generated inside the panel

collects.

• Leave sufficient space above and below the Machine Controller, and maintain adequate distances from other devices,

cable ducts, and other objects to ensure suitable air circulation.

• Do not mount the Machine Controller in any direction other than the specified direction.
• Do not mount the Machine Controller on top of any device that generates a significant amount of heat.
• Do not subject the Machine Controller to direct sunlight.

„

Control Panels with Forced-air Cooling

Install a fan near the center of and at the top or bottom of the Machine Controller for either of the following methods.

• Forced draft method (A fan or a similar device is used to circulate the air in the interior and the exterior of the panel.).
• Forced circulation method (A fan or a similar device is mounted to the airtight panel to circulate the air inside.).

Note: 1. Use the following guideline when selecting the fan:

• 80 x 80 mm min., Maximum air flow: 0.9 m

3

/min, Maximum static pressure: 26.5 Pa or higher.

2. Adjust the fan installation location and the direction of air flow as shown in

Figure 8

.

Figure 8

Figure 8 Fan installation location and air flow direction

Fan

Fan

40 mm min.

10 mm

min.

*

* For a control panel with natural cooling with the MBU-303 Base Unit: 30 mm min.

10 mm

min.

*

40 mm min.

Approx.
40 mm

Direction
of air flow

Direction
of air flow

Approx.
40 mm