YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7

8 Switches

8

Switches

The CPU Module has the following two types of switches.

• DIP switches: Mode switches
• STOP/SAVE switch

‹

DIP Switches: Mode Switches

The SW1 and SW2 switches are checked at start-up, and their behavior is described in the following tables:

Table 3 SW1 Switches

Table 4 SW2 Switches

E-INIT and - switches can override the Ethernet configuration according to

Table 5

.

Table 5 Operation of E-INIT, E-PM0 and E-PM1 for Configuring Ethernet

On start-up, the controller will automatically load firmware or user projects based on the LOAD and MNT switches. The
USB thumb drive is available in any other circumstances.

Table 6 Operation of LOAD and MNT for USB Thumb Drive

SW

Description

STOP

When ON, prevents PLC from running.

E-INIT

When ON, overrides Ethernet configuration according to

Table 5

.

INIT

When ON, the controller uses the fixed, default configuration

CNFG

When ON, the controller creates Axes and I/O for all connected devices. (Auto-configuration)

SW

Description

LOAD

When ON, load either the user project or firmware from the USB thumb drive. See

Table 6

for details.

TEST

When ON, the IP address is scrolled across the seven segment display.

MNT

When ON, controller starts up in supervisor mode. In this mode MECHATROLINK III, PLC, Modbus/TCP and Ethernet/IP
do not start. The controller firmware can be updated, and clearing DOS FS alarms will repair the DOS FS.

-- / DHCP

DHCP Selection when E-INIT is ON.

E-INIT

-- / DHCP

Static Configuration

OFF

N/A

192.168.1.1

ON

OFF

DHCP

ON

ON

E-INIT

-- / DHCP

Load user project from USB thumb drive

ON

OFF

Install firmware and user project from USB

thumb drive

ON

ON