SMA Solar Technology AG

5 Electrical Connection

Installation Guide

Ukonstanter-IEN103610

15

• Replace it with a matching type D line circuit breaker.

5.3 Inserting the Cables

Required cables:

☐ 2 x 1.5 mm

2

cable for temperature monitoring

☐ 3 x 4 mm

2

cable for the 230 V circuit, maximum cable length: 7 m

☐ 2 x 4 mm

2

cable for the 415 V circuit

☐ 1 x 4 mm

2

PE cable for the enclosure

Figure 8: Cable glands on the side

/05*$&

Flashover along the surface of the cable insulation.

• Use separate cable channels for the 230 V circuit and the 415 V circuit in order to ensure

sufficient insulation between the two circuits.

Position

Description

A

Cable gland for temperature monitoring

B

Cable gland for 415 V circuit and the protective conductor cable

C

Cable gland for the 230 V circuit