3 integrating the inverter into the network, 4 configuring the country data set, Integrating the inverter into the network – SMA SB 1300TL User Manual
Page 41: Configuring the country data set

☐ A communication product corresponding to the type of communication used must be
available.
☐ The inverter must be registered in the communication product.
☐ The changes to the grid-relevant parameters must be approved by the responsible grid
operator.
☐ When changing grid-relevant parameters, the SMA Grid Guard code must be available (see
the Certificate "Order Form for the SMA Grid Guard Code" at
Procedure:
1. Call up the user interface of the communication product or software and log in as Installer or
User.
2. If required, enter the SMA Grid Guard code.
3. Select and set the required parameter.
4. Save settings.
8.3
Integrating the Inverter into the Network
If the router supports DHCP and DHCP is enabled, the inverter will automatically be integrated into
the network. You will not need to carry out network configuration.
If the router does not support DHCP, automatic network configuration will not be possible and you
will need to use SMA Connection Assist to integrate the inverter into the network.
Requirements:
☐ The inverter must be in operation.
☐ There must be a router with Internet connection in the local network of the system.
☐ The inverter must be connected to the router.
Procedure:
• Integrate the inverter into the network by means of the SMA Connection Assist. Download the
SMA Connection Assist and install it on the computer (see
8.4
Configuring the Country Data Set
By default, the inverter is set to a specific country data set. You can find the country data set to
which the inverter has been set on the enclosed supplementary sheet with the default settings or on
the type label. Each country data set contains various operating parameters which can be
individually set according to the respective country. You can change the parameters by means of a
communication product.