beautypg.com

5 mounting, 1 requirements for mounting, Mounting – SMA SB 1300TL User Manual

Page 16: Requirements for mounting, 5mounting

background image

5

Mounting

5.1

Requirements for Mounting

Requirements for the mounting location:

Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.

• Do not mount the inverter in areas containing highly flammable materials or gases.
• Do not mount the inverter in a potentially explosive atmosphere.

☐ The mounting location must be inaccessible to children.
☐ A solid support surface must be available for mounting, e.g. concrete or masonry. When

mounted on drywall or similar materials in the living area, the inverter emits audible vibrations
during operation which could be perceived as annoying.

☐ The mounting location must be suitable for the weight and dimensions of the inverter (see

Section 11 "Technical Data", page 48).

☐ To ensure optimum operation, the ambient temperature should be between -25°C and 40°C.
☐ The mounting location should not be exposed to direct solar irradiation. Direct solar irradiation

can cause the inverter to overheat. As a result, the inverter reduces its power output.

☐ Climatic conditions must be met (see Section 11 "Technical Data", page 48).
☐ The mounting location should be freely and safely accessible at all times without the need for

any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.

5 Mounting

SMA Solar Technology AG

Operating Manual

SB13-21TL-BE-en-11

16

This manual is related to the following products: