Grid feeding with the SMA Power Balancer

SMA America, LLC

12

SBUS-PowBal-IUS102810

Installation Guide

4 Grid feeding with the SMA Power Balancer

The SMA Power Balancer enables a circuit connection of 3 inverters to a three-phase grid-feed
system.

Connection to a three-phase system, 208 V/240 V

• One inverter connected to L1, L2 and N, if present.
• One inverter connected to L2, L3 and N, if present.
• One inverter connected to L1, L3 and N, if present.

Connection to a three-phase system, 277 V

• One inverter connected to L1 and N.
• One inverter connected to L2 and N.