beautypg.com

Network requirements, Configuration procedure – H3C Technologies H3C MSR 5600 User Manual

Page 27

background image

20

Backup FEP configuration example (transparent mode)

Network requirements

In transparent mode, a pair of primary and backup FEPs can provide service for only one POS terminal.
As shown in

Figure 11

, FEP-A (primary FEP) and FEP-B (backup FEP) provide service for the AM POS

terminal. If FEP-A is unreachable, FEP-B is used.
The FEPs have POS access enabled and use the listening port 2000.

Figure 11 Network diagram

Configuration procedure

1.

Enable the POS access service.

system-view

[RouterA] posa server enable

2.

Configure application template 1:
# Configure application template 1 in TCP mode.

[RouterA] posa app 1 type tcp

# Specify FEP-A with IP address 2.2.2.1 and port number 2000 for application template 1.

[RouterA-posa-app1] ip 2.2.2.1 port 2000

# Specify application template 2 as the backup application template.

[RouterA-posa-app1] backup app 2

# Set the quiet timer for POS application template 1 to 10 minutes.

[RouterA-posa-app1] timer quiet 10

[RouterA-posa-app1] quit

3.

Configure POS application template 2:
# Configure application template 2 in TCP mode.

[RouterA] posa app 2 type tcp

# Specify FEP-B with IP address 2.2.2.2 and port number 2000 for POS application template 2.

[RouterA-posa-app2] ip 2.2.2.2 port 2000

[RouterA-posa-app2] quit

4.

Configure the AM POS terminal template:
# Configure interface AM 5/0 as the access interface of terminal template 12. Specify terminal
template 12 to use POS application template 1 to transparently transport packets of the terminal.

[RouterA] interface analogmodem 5/0

[RouterA-Analogmodem5/0] posa bind terminal 12 app 1

[RouterA-Analogmodem5/0] quit