Configuring temperature thresholds for a card – H3C Technologies H3C S9500E Series Switches User Manual
Page 69

59
Configuring temperature thresholds for a card
You can set temperature thresholds for a card. When the temperature of a card reaches the threshold, the
switch generates alarms.
Configuring temperature thresholds for a card
Step Command
1.
Enter system view.
system-view
2.
Configure temperature
thresholds for a card.
•
In standalone mode:
temperature-limit slot slot-number { inflow | hotspot | outflow } sensor-num
lowerlimit warninglimit [ alarmlimit ]
•
In IRF mode:
temperature-limit chassis chassis-number slot slot-number { inflow | hotspot |
outflow } sensor-num lowerlimit warninglimit [ alarmlimit ]
Displaying the temperature information on your switch
Use the display environment command to display the temperature information of the sensors on the cards,
including the current temperature and temperature thresholds.
# Display the temperature information of the cards on the switch.
•
In standalone mode:
System temperature information (degree centigrade):
-------------------------------------------------------------------------------
Slot Sensor Temperature LowerLimit WarningLimit AlarmLimit ShutdownLimit
0 inflow 1 26 -10 55 85 N/A
0 outflow 1 30 5 75 90 N/A
0 hotspot 1 29 0 70 85 N/A
0 hotspot 2 30 20 80 95 N/A
3 inflow 1 26 -10 55 75 N/A
3 outflow 1 28 -5 65 85 N/A
3 hotspot 1 28 -5 65 85 N/A
•
In IRF mode:
System temperature information (degree centigrade):
-------------------------------------------------------------------------------
Slot Sensor Temperature LowerLimit WarningLimit AlarmLimit ShutdownLimit
1/0 inflow 1 25 -10 55 85 N/A
1/0 outflow 1 31 5 75 90 N/A
1/0 hotspot 1 29 0 70 85 N/A
1/0 hotspot 2 32 20 80 95 N/A
1/3 inflow 1 25 -10 55 75 N/A
1/3 outflow 1 28 -5 65 85 N/A
1/3 hotspot 1 31 -5 65 85 N/A