3

Wire the Click 210 circuit breaker

Follow the steps below to add a Click 210 circuit breaker

and switch:
1 Mount the Click 210 onto the DIN rail.

2 Connect power in to the bottom of the module.

3 Connect power out to the top of the module.

4

Wire the Click 230 AC surge

Follow the steps below to install the AC surge protection:
1 Mount the Click 230 onto the DIN rail.

2 Connect the line (hot) wire from the Click 210 to terminal 5

on the IN side of the Click 230.

3 Connect the neutral wire from the AC terminal block or

cord to the terminal marked 1 on the Click 230.

4 Connect the ground wire from the AC terminal block or

cord to the terminal marked 3 on the Click 230.

5 Connect the outgoing and protected neutral wire to the

terminal marked 2 on the Click 230.

6 Connect the outgoing and protected line wire to the terminal

marked 6 on the Click 230.

7 Terminal blocks 3 and 4 are directly connected to the DIN

rail via the metal mounting foot on the base of the device.

There is no need for any additional grounding between ter-

minals 3 and 4 and the DIN rail.