Select a driver
1 Select Setup Click on the main screen.
2 Select the appropriate driver for your application:
˽
SmartSensor – If you connect from a TOC to Click 301 to sensor
˽
Point to Point – If you connect from a TOC to Click 301 to another Click
301 to sensor
˽
Expert – Use only when instructed to by Wavetronix Technical Services
3 Click OK.
Once that driver has loaded, you can use it to change function settings such as
baud rate as well as to change informational settings such as device location and
description. You can also use the driver to view device information such as serial
number and firmware version.
7
Configure the module
Change the appropriate settings below. Only the IP address and port–related settings are necessary for
device functionality.
SmartSensor Driver
˽
Description/Location – For informational/identification purposes only.
These settings do not affect the operation of the device.
˽
Device ID – Changes the ID number associated with the device. By default
this is the last five digits of the serial number.
˽
Baud rate – If connecting to a sensor, this must match the sensor’s baud rate.
˽
IP Address – Change this setting to the desired IP address of the device.
Default is 172.16.0.13.
˽
IP Port – Change this setting to the desired IP port of the device. Default is
10001.
Point to Point Driver
˽
Description/Location – For informational/identification purposes only.
These settings do not affect the operation of the device.
˽
Device ID – Changes the ID number associated with the device. By default
this is the last five digits of the serial number.
˽
Baud rate – If connecting to a sensor, this must match the sensor’s baud rate.
˽
IP Address / IP Port – See SmartSensor driver above.
˽
Remote IP Address – Change this setting to the IP address of the device you
want your device to connect to. Default is 172.16.0.14.
˽
Remote IP Port – Change this setting to the IP port of the device you want
your device to connect to. Default is 10001.