beautypg.com

Install click supervisor, Make a connection, Select a driver – Wavetronix Click 400 (900 MHz radio) (CLK-400) - Quick-reference Guide User Manual

Page 3: Configure the module

background image

5

Install Click Supervisor

Click Supervisor will be used to configure the Click 400. To install it:
1 Download the setup file from www.wavetronix.com (under Support).

2 Double-click on the file to run the setup wizard. Follow the steps to install.

6

Make a connection

1 Make sure there is a connection between the Click 400 and the computer that

Click Supervisor is on. This can be through the DB-9 connector on the module

or through another device also on the T-bus; for example, the Click 421 can

communicate with the computer through Bluetooth®.

2 Run Click Supervisor and select Communication. The Click 400 can only be

configured using serial communication.

3 Click Settings to make any necessary changes to the settings, such as the port or

the baud rate. Click OK to return to the Communication screen, then click Con-

nect. Keep the Click ID set to 0.

4 In the next screen, Click Supervisor will display all the devices it discovers.

When the Click 400 appears, select it and click Select. Click Supervisor will connect to the device.

7

Select a driver

1 Select Setup Click on the main screen.

2 Select the appropriate driver for your application:

˽

Client – If you connect multiple clients to a

single server

˽

Server – If you connect a single radio to another

single radio

˽

SmartSensor Client – If you connect a wireless

sensor station to a wireless base station

˽

SmartSensor Server – If you connect a wireless

base station to a wireless sensor station

˽

Expert – Use only when instructed to by Wa-

vetronix Technical Services

3 Click OK.

Once that driver has loaded, you can use it to change functional and informational settings.

8

Configure the module

Change any necessary settings in the Setup tab (RF channel may be the only one that needs changing).

˽

Description/Location – For informational/identification purposes only.

˽

Device ID – Changes the ID number associated with the device. By default this is

the last five digits of the serial number.

˽

RF Channel – The frequency channel of the device. If you perform a link test, each

client and server must be on the same channel.

˽

Tx Power – Lets you modify the transmit power level.

˽

Baud Rate – If connecting to a sensor, this must match the sensor’s baud rate.