beautypg.com

Gpc-17 wiring, Component & system wiring 54, Optional analog output board – WattMaster VAV User Manual

Page 54: Gpc-17 controller, Optional relay expansion board, Ribbon connector

background image

Component & System Wiring

54

Note:
Set-up, Programming
And Monitoring Of
The GPC-17
Controller Requires
The Use Of A
Personal Computer
And Prism Software.

1.)24 VAC Must Be Connected So

That All Ground Wires Remain
Common.

3.)All Communication Wiring To Be 18

Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.

4.)It Is Recommended That All

Controllers Address Switches Are
Set Before Installation.

2.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

Local Loop RS-485

Communications To Other

Controllers

And/Or System Manager

Ribbon Connector

Optional
Analog
Output
Board

Ground

24V

All switches
(1 thru 4)
must be in the
“ON” position

EPROM

RAM

PAL

PIN 1

PIN 1

PIN 1

PIN 1

CPU

+V
+V

1

3
4
5
6
7
8

G
G

2

ANALOG

INPUTS

GND

SIG

+5V

ANALOG

OUTPUTS

A1

A2

G

T

SH

R

GND

24VAC

GPC-17 Controller

T

SH

R

K1

R1

R2

R3

R4

R5

R6

R7

R8

K2

K3

K4

K5

K6

K7

Line Voltage

Line Voltage

See Note 1

16

8

4

2

1

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller
Address Switch

This Switch Must Be
In The ON Position
As Shown

These Switches Should Be
In The OFF Position
As Shown

ADD

ADD

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop

Required VA For Transformer

Each Controller = 10 VA Min.

Note:

All Circuit Board
Contacts Are N.O.
All Contacts Are
Rated For 2 Amps
@ 24VAC Pilot
Duty Only
Do Not Apply Any
Voltage Greater
Than 24VAC

!

!

!

Caution!
Controller Must Have Address Switch Set Between 1 and 60

24V

COM

ANALOG OUT1

ANALOG OUT2

W

A

TTMASTER

ANALOG

OUTPUT

BOARD

YS101428

REV

.1

ADDR

+

-

+

-

1

2

LD1

PWR

ANALOG OUT3

ANALOG OUT4

+

-

+

-

RN1

Optional Relay Expansion Board

Relay Outputs
To Devices As
Required
By Application

Analog Inputs And/Or
Digital Inputs
From Devices As
Required By
Application

Relay
Outputs to
Devices
As
Required
By
Application

Analog Output
To Device
(0-10 VDC)

FILENAME

DATE:

DESCRIPTION:

PAGE

DRAWN BY:

GPC-17 Controller

1

JOB NAME

W-GPC-17CNTRL1A.CDR

OE310-21-GPC

B. Crews

05/12/04

C

O

N

T

R

O

L

S

Ribbon Connector

GPC-17 Wiring