background image

Component & System Wiring

24

4-20

mA

4-20

mA

V

A

Co

rD

C

V

A

Co

rD

C

GNDGND

0-5V

or

0-10V

0-5V

or

0-10V

4 4

4 4

5 5

6 6

ON

ON

ON

ON

3 3

3 3

2 2

2 2

1 1

1 1

Zero

Zero

Span

Span

Notes:

1.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

WMVAV Controller Wiring

JOB NAME

02/21/08

VAV-HumidSensorWire1B.CDR

Humidity Sensor To

1

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Outdoor

Air Humidity

Sensor - 4-20mA

WMVAV Controller Board

250 Ohm

Resistor

(Shipped With Sensor)

To be Installed Between

AIN5 and GND

Note:
If Remote Occupied Contact Is
Required When Humidity
Sensor Is Used, The Remote
Occupied Contact Must Be
Relocated To AIN2 On The 4
Analog Input 1 Analog Output
Expansion Board.

The Pull-up Resistor (PU5)
Must Be Removed
When Using A 4-20ma Device

Warning:

It is very important to be certain that all wiring

is correct as shown in the wiring diagram

below. Failure to observe the correct polarity

will result in damage to the Humidity Sensor or

controller.

Humidity Sensor Wiring