9 fixed frequency (ff), 10 jog – Watson-Marlow MM420 User Manual
Page 78

3 Functions
Issue 10/06
MICROMASTER 420 Operating Instructions
78
6SE6400-5AA00-0BP0
3.5.5.9
Fixed frequency (FF)
P1001 =...
Fixed frequency 1
Can be directly selected via DIN1
(P0701 = 15, 16)
P1002 =... Fixed frequency 2
Can be directly selected via DIN2
(P0702 = 15, 16)
P1003 =... Fixed frequency 3
Can be directly selected via DIN3
(P0703 = 15, 16)
P1004 =... Fixed frequency 4
P1005 =... Fixed frequency 5
P1006 =... Fixed frequency 6
P1007 =... Fixed frequency 7
When defining the function of the digital inputs
(P0701 to P0703), three different types can be
selected for fixed frequencies:
15 = Direct selection (binary-coded)
In this particular mode, the appropriate
digital input always selects the associated
fixed frequency, e.g.:
Digital input 3 = selects fixed frequency 3.
If several inputs are simultaneously active,
then these are summed. An ON command is
additionally required.
16 = Direct selection + ON command
(binary-coded + On / Off1)
In this mode, the fixed frequencies are
selected as for 15, however these are
combined with an ON command.
17 = Binary coded selection + ON command
(BCD-coded + On/ Off1)
The BCD-coded operating mode is effective
for digital inputs 1 to 3.
P1016 =... Fixed frequency code –
Bit 0
Defines the selection method for fixed
frequencies.
P1017 =... Fixed frequency code –
Bit 1
P1018 =... Fixed frequency code –
Bit 2
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
NOTE
For settings 2 and 3, all parameters P1016 to
P1019 must be set to the selected value so that
the drive inverter accepts the ON command.
3.5.5.10 JOG
P1058 =...
JOG frequency right
Frequency in Hz when the motor is being
jogged in the clockwise direction of rotation.
P1059 =...
JOG frequency left
Frequency in Hz when the motor is being
jogged in the counter-clockwise direction of
rotation.
P1060 =...
JOG ramp-up time
Ramp-up time in s from 0 to the maximum
frequency (P1082). The JOG ramp-up is
limited by P1058 or P1059.
P1061 =...
JOG ramp-down time
Ramp-down time in s from the maximum
frequency (P1082) to 0.
P1082
(f
max
)
P1058
t
P1060
P1061
f
JOG
5.00 Hz
10.00 Hz
15.00 Hz
20.00 Hz
25.00 Hz
30.00 Hz
0.00 Hz
1
1
1
10.00 s
10.00 s
5.00 Hz
5.00 Hz