3.1.2.3 BICO
technology
Using BICO technology (English: Binector Connector Technology), process data
can be freely interconnected using the "standard" drive parameterization. In this
case, all values which can be freely interconnected (e.g. frequency setpoint,
frequency actual value, current actual value, etc.) can be defined as "Connectors"
and all digital signals which can be freely interconnected (e.g. status of a digital
input, ON/OFF, message function when a limit is violated etc.) can be defined as
"Binectors".
There are many input and output quantities as well as quantities within the control
which can be interconnected in a drive unit. It is possible to adapt the drive to the
various requirements using BICO technology.
A binector is a digital (binary) signal without any units and which can either have
the value 0 or 1. Binectors always refer to functions whereby they are sub-divided
into binector inputs and binector outputs (refer to Fig. 3-4). In this case, the
binector input is always designated using a "P" parameter plus attribute "BI" (e.g.:
P1035 BI: Enable MOP (UP-command)), while the binector output is always
represented using an "r" parameter plus attribute "BO" (e.g.: r2032 BO: CtrlWrd1
from BOP link (USS)).
As can be seen from the examples above, the binector parameters have the
following abbreviations in front of the parameter names:
BI Binector Input, signal receiver ("P" parameters)
→ The BI parameter can be interconnected with a binector output as source, by
entering the parameter number of the binector output (BO parameter) as
value in the BI parameter.
BO Binector Output, signal source ("r" parameters)
→ The BO parameter can be used as source for BI parameters. For the
particular interconnection the BO parameter number must be entered into
the BI parameter.
Example:
Wiring BO parameter r2032 to BI parameter P1035
→ P1035 = 2032.
If the BO parameter contains several bits, the bit number must be entered in the
BI parameter in addition to the parameter number when wiring a single digital
signal (here for example: P1035 = 2032.13).
Abbreviation and symbol
Name
Function
BI
Binector input
(signal receiver)
Data flow
Pxxxx
BI: ...
Function
BO
Binector output
(signal source)
Data flow
Function
rxxxx
BO: ...
Fig. 3-4
Binectors