3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
103
The telegram has the following structure:
Each telegram begins with the start character STX (= 02 hex), followed by the
length information (LGE) and the address byte (ADR). The net characters then
follow. The telegram is terminated by the BCC (Block Check Character).
For single-word data (16 bit) in the net data block (= net character block), the
high byte (first character) is always sent and then the low byte (second
character).
The same applies to double-word data: the high word is sent first followed by
the low word.
The necessary settings / parameter assignments must be made both at the
master as well as at the slave and can no longer be changed in bus operation.
The protocol does not identify tasks in the net characters. The contents of the
net characters/data for the MICROMASTER drives is discussed in Section
3.7.1.2 "Structure of the net data".
n net characters
STX
LGE
ADR
1.
2.
n
BCC
Fig. 3-32
Telegram structure
Information is coded as follows:
Abbreviation Significance
Size
Explanation
STX
Start of text
ASCII characters
02 hex
LGE
Telegram length
1 byte
Contains the telegram length
ADR
Address
1 byte
Contains the slave address and the
telegram type (binary coded)
---
Net characters
Each one byte
Net data, contents are dependent on
the request
BCC Block
check
character
1 byte
Data security characters