6 analog input (adc) – Watson-Marlow MM420 User Manual
Page 75

Issue 10/06
3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
75
3.5.5.6
Analog input (ADC)
P0757 =...
Value x1 of ADC scaling
P0758 =...
Value y1 of ADC scaling
This parameter represents the
value of x1 as a % of P2000
(reference frequency).
P0759 =...
Value x2 of ADC scaling
P0760 =...
Value y2 of ADC scaling
This parameter represents the
value of x2 as a % of P2000
(reference frequency).
P0761 =... Width of ADC deadband
Defines width of deadband on
analog input.
max
100 %
10 V
V
x
100%
%
P0760
P0758
P0759
P0761 > 0
0 < P0758 < P0760
||
0 > P0758 > P0760
min
P0757
P0761
P0757 = P0761
4000 h
KL
KL
A
D
ADC
type
ADC
scaling
ADC
dead
zone
r0755
Pxxxx
r0752
P1000
ADC
ADC+
r0754
P0761
P0753
P0756
Setpoint
r0722
r0722.3
0
1
1.7 V
3.9 V
F0080
P0704
Pxxxx
Function
Wire
breakage
sensing
P0756
P0761
T
0
P0762
r0751
r0751
0 V
0.0 %
10 V
100.0 %
0 V