Watson-Marlow MM420 User Manual
Page 188

5 MICROMASTER 420 specifications
Issue 10/06
MICROMASTER 420 Operating Instructions
188
6SE6400-5AA00-0BP0
Input voltage range
3 AC 200 V – 240 V, ± 10 %
(Unfiltered)
Order No.
6SE6420- 2UC11-
2AA1
2UC12-
5AA1
2UC13-
7AA1
2UC15-
5AA1
2UC17-
5AA1
2UC21-
1BA1
2UC21-
5BA1
2UC22-
2BA1
[kW] 0.12 0.25 0.37 0.55
0.75 1.1 1.5 2.2
Output Rating
[hp] 0.16 0.33 0.5 0.75 1.0 1.5 2.0 3.0
Output Power
[kVA]
0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6
Input
Current
1) [A] 1.1 1.9 2.7 3.6 4.7 6.4 8.3 11.7
Output
Current
[A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4
Fuse
[A] 10 10 10 10 10 16 16 20
Recommended 3NA 3803 3803 3803 3803 3803 3805 3805 3807
For UL specified
* * * * * * * *
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Input Cable, min.
[awg]
18 18 18 18 18 18 18 18
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0
Input Cable, max.
[awg]
14 14 14 14 14 10 10 10
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Output Cable, min.
[awg]
18 18 18 18 18 18 18 18
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0
Output Cable, max.
[awg]
14 14 14 14 14 10 10 10
[kg] 1.2 1.2 1.2 1.2 1.2 2.9 2.9 3.1
Weight
[lbs] 2.6 2.6 2.6 2.6 2.6 6.4 6.4 6.8
Order No.
6SE6420- 2UC23-
0CA1
2UC24-
0CA1
2UC25-
5CA1
[kW] 3.0 4.0 5.5
Output Rating
[hp] 4.0 5.0 7.5
Output Power
[kVA]
6.0
7.7 9.6
Input Current 1)
[A]
15.6 19.7 26.5
Output Current
[A]
13.6
17.5
22.0
Fuse [A]
25
32
35
Recommended 3NA
3810
3812
3814
For UL specified
* * *
[mm
2
] 2.5 2.5 4.0
Input Cable, min.
[awg] 14 14 12
[mm
2
] 10.0 10.0 10.0
Input Cable, max.
[awg] 8 8 8
[mm
2
] 1.5 2.5 4.0
Output Cable, min.
[awg] 16 14 12
[mm
2
] 10.0 10.0 10.0
Output Cable, max.
[awg] 8 8 8
[kg] 5.2 5.5 5.5
Weight
[lbs] 11.4 12.1 12.1
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America