Installation Guide
KoldLok
®
24” Extended Raised Floor Grommet
General Information
Effective Installation of Cables
In order to minimize any air loss from under the raised-floor plenum, allow for adequate
slack in the cables. If the cables are under too much tension, the Grommet filaments may
be pulled apart, resulting in a V-shaped gap that will cause an increase in the volume of air
escaping from under the raised floor.
Cutting Raised Floor Tiles
Each raised floor tile manufacturer provides instructions to properly and safely modify their
products. Installers must be familiar with and observe tile manufacturer’s recommendatios
with regard to applicable tools, cutting procedures, the design load capacity of the cut tile,
and any additional underfloor support requirements for cut raised floor tiles.
When installing the KoldLok Extended Raised Floor Grommet on a newly cut hole, trim
the cutout prior to installation.
Maintaining Proper Cooling of Equipment
Failure to follow computer manufacturer’s guidelines for maintaining proper cooling may
result in the overheating of equipment. Before sealing gaps between racks, ensure that
there is adequate airflow to the intake side of the computer equipment or cabinets through
devices such as perforated floor tiles or grates. Achieving proper airflow to the intake side of
computer equipment and/or cabinets is the responsibility of the customer.
Safety Requirements
Installers must be familiar with standard safety and risk management practices when work-
ing on server rack equipment or in data center environments.