beautypg.com

Installation procedure with adhesive mounting kit – Upsite 10013 Extended 6 x 24 Brush User Manual

Page 4

background image

4

Designer & Manufacturer

(888) 982-7800 www.upsite.com

Designer & Manufacturer

(888) 982-7800 www.upsite.com

Installation Procedure with Self-Tapping Screws Continued:

4. Align the screw holes of one End Cap with the screw holes on the end of the Grommet

flange. Use self-tapping screws to attach the End Cap and flange to the floor tile. The
screw-hole design allows for horizontal and vertical positioning of the End Caps when
attaching to the flange. NOTE: With the inside wall of the End Caps mounted against the
flange, the installed Grommet can seal an opening the length of a 600mm floor tile. With
the End Caps extended away from the flange, the installed Grommet can seal an opening
the length of a 24-inch floor tile.

5. Repeat Step 4 with the other End Cap.

6. Attach the Grommet with the remaining screws.

7. Clean any residue that may have been created during installation.

Installation Procedure with Adhesive Mounting Kit

(see Figure 2)

:

1. Remove one layer of adhesive backing from each of the three pads and mount on the bot-

tom of the flange at the center and outside corners in a vertical position.

2. Remove one layer of adhesive backing from each of the four 5-inch strips. Mount strips

between each vertical pad, along the rear edge of the flange that is furthest away from
the brush holders.

3. Remove the second layer of adhesive backing from all seven adhesive strips. Position the

Grommet on the floor tile and over the cable cutout.

4. Adhere the unit to the floor. Press down firmly on all portions of the unit to ensure a se-

cure connection to the raised floor surface.

5. Use the two strips of thin double-sided adhesive to adhere the left and right End Caps to

the top of the flange.

6. Mount the End Cap

Figure 2: Assembled Adhesive Mounting Kit