beautypg.com

Tubetrace, Tubing bundles, Installation procedures – Thermon TubeTrace Tubing Bundles User Manual

Page 6: Tubing bundle attachment methods, Illustration e: typical vertical attachment

background image

Table 2: Strut Clamp Selection

Nominal Bundle O.D.

Strut Clamp Size

25mm

32mm

32mm

38mm

41mm

51mm

67mm

64mm

86mm

76mm

92mm

89mm

Tubing Bundle Attachment Methods . . .

1. For ease on installation and maintenance, route multiple

runs of TubeTrace tubing bundles symmetrically utilizing
the most accessible path possible. Routing should take
advantage of existing cable trays, angles, channels, struts
and I-beams for support. Maintain a 76mm minimum
clearance between lines. Do not secure bundles to each
other.

2. After pulling bundle into position, insure suffi cient

bundle is available to make fi nal connections. Secure top
Kellems grip to support structure, with additional Kellems
grips located every 10.67m.

3. Allow expansion loop in tray every 30m for expansion

and contraction of TubeTrace tubing bundle. Provide
300mm of slack for every 30m of tubing bundle.

4. Secure TubeTrace tubing bundles to support structure

every 1.5 to 1.8m on horizontal straight runs and every
3 to 4.5m on vertical runs. Provide additional support
within 450mm of any connection point or transition
fi tting and within 150 to 250mm of any bends.

5. Cable trays and channel struts provide optimal support

for multiple passes of TubeTrace tubing bundle. Secure
bundle to cable tray using UV resistant plastic cable ties,
or preferably stainless steel bundle clamps or standard
conduit straps for channel strut attachment (see Table
2 for clamp sizing). Use caution when securing bundle
to structure. Do not deform or crush the thermal
insulation and outer jacket.

6. As an option, angle iron may be used to support

TubeTrace tubing bundles on long vertical and horizontal
runs. Angle iron should be sized approximately 12mm
larger than the tubing O.D. Place the angle over the
bundle to prevent moisture buildup. Secure bundle to
the angle using UV resistant cable ties or stainless steel
banding.

Illustration E: Typical Vertical Attachment

Kellems Grip

Channel Strut

or Cable Tray

(Typical)

Angle Iron, Channel

I-Beam (Typical)

Strut Clamp

(Typical)

Secure Bundle with

Kellems Grip Located

Every 10.67m

(Typical)

TubeTrace

Tubing Bundle

(Typical)

5

7. Before making power connection, the heat trace should

be tested to ensure electrical integrity with at least a 500
Vdc megohmmeter (megger) between the heat trace
bus wires and the metallic braid. IEEE 515 recommends
that the test voltage for polymer insulated heat trace be
2500 Vdc. Minimum resistance should be 20 megohms.
(Record 2 on Field Test Report)

After the power

connection is completed, temporarily energize heat
trace so that the energized test values can be recorded.
(Record 3 on Field Test Report)

UV Resistant

Plastic Cable Ties

(Typical)

TubeTrace

®

Tubing Bundles

INSTALLATION PROCEDURES

This manual is related to the following products: