8 - Technical Specifications
Features
at 25°C env. temp.
Description
Algorithm
PID with overshoot control or On-off - PID with valve drive algorithm, for controlling motorised positioners
Proportional band (P)
0.5…999.9%
Single action
PID algorithm
Integral time (I)
1…9999 s
OFF
= O
Derivative time (D)
0.1…999.9 s
Error dead band
0.1…10.0 digit
Overshoot control
0.01…1.00
Manual reset
0…100%
Cycle time (Time proportional only)
0.2…100.0 s
Min./Max output limits
0…100% separately adjustable
Soft-start output value
1…100% - Time 1…9999 s
Control mode
Output safety value
-100…100%
Control output hysteresis
0…5% Span in engineering units
On-Off algorithm
Dead band
0.0…5.0%
Double action
PID algorithm
(Heat / Cool)
Cool proportional band (P)
0.5…999.9%
Cool integral time (I)
1…9999 s
OFF
= O
Cool derivative time (D)
0.1…999.9 s
Cool cycle time (Time proportional only) 0.2…100.0 s
Control output high limit
0…100%
Motor travel time
15…600 s
Valve drive PID algorithm
Raise/Stop/Lower
Motor minimum step
to 0.1…5.0%
Control output forcing value
-100…100%
Feedback potentiometer
100
Ω …10kΩ
Control output rate limit
0.01…99.99%/s
OFF
= O
Cool output max. rate
0.01…99.99%/s
OFF
= O