4 - Operation
TIMER COUNTING MODES
D - Counting start time = timer launch time,
end with control output forced to zero.
The time counting starts when the timer is
launched. At the end, the control output is
forced to zero [1].
F - Control action with stand-by Setpoint
during the counting time.
The time counting starts when the timer is
launched and the control action use the
Stand-by Setpoint. At the end, the control
action use the working Setpoint.
E - No control action during
the counting time.
The time counting starts when the timer is
launched and the control output is forced to
zero. At the end, the control action starts.
tdop
= 1
tdop
= 0
#tiMe
Timer launch
#t.Mod
= 5
Process
variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
tdop
= 1
tdop
= 0
#tiMe
Timer launch
SP
#t.Mod
= 6
Process
variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
tdop
= 1
tdop
= 0
#tiMe
Timer launch
#s.p. 2
#t.Mod
=7
SP
Process
variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
Notes
[1] When the Timer is not running the control output is forced to zero.
[2] When the PID enable parameter is set to “0” (PID disabled) the OP output is set to “0”.