Hy-d #hy-u – Super Systems X5 User Manual
Page 48
48
4 - Operation
4.5.2 ALARM MENU
(see also pages 32 and 33)
Asymmetric
upper alarm
hysteresis
Asymmetric
lower alarm
hysteresis
The parameter can be set
between 0 and 5% of the con-
figured Span and set in
Engineering units. e.g.
Range =
-200…600°C
Span
= 800°C
Max. Hysteresis = 5% 800°= 40°C
For symmetrical hysteresis set
#hy-d
=
#hy-u
#hy-d
#hy-u
Alarm
delay
Delay time for alarm activation.
OFF
: alarm activated immediately
1...9999 seconds: alarm acti-
vated only if the condition per-
sists for the set time
#tF1
4.5.1 SETPOINT MENU
If SR starting point is lower
than the ending point, both
expressed in engineering units:
If SR starting point is higher
than the ending point, both
expressed in engineering units
Working Setpoint (SP) as com-
bination of Local Setpoint (SL)
and remote signal
Setpoint
Loc.t
(table 3, page 27)
Setpoint
reM.t
(table 3, page 27)
E.g.: Local Setpoint (SL) with an
external Trim with multiply-
ing coefficient of 1/10:
Setpoint type =
Loc.t
rtio
= 0.1;
biaS
= 0
Remote Setpoint (SR) with an
internal Trim with multiplying
coefficient of 1/5:
Setpoint type =
reM.t
rtio
= 0.2;
biaS
= 0
Remote Setpoint range equal to
the Input range:
Setpoint type =
Loc.t
rtio
= 1;
biaS
= LR
SL
= 0
biaS
=
starting point = a
rtio
=
E.g.: biaS= 20
rtio
=
b - a
HR - LR
100 - 20
600 - (-200)
80
800
= 0.1
=
biaS
=
starting point = a
´
rtio
=
E.g.: biaS= 100
rtio
=
b
´
- a
´
HR - LR
20 - 100
600 - (-200)
-80
800
= -0.1
=
=
Example with high absolute alarm
#hy-d
Alarm threshold
#hy-u
On
Off
SP = SL + (rtio • REM) + biaS
SP = REM + (rtio • SL) + bias
SIGN = Remote signal %
SPAN = HR-LR
REM =
SIGN * SPAN
100