Super Systems X5 User Manual
Page 21
![background image](https://www.manualsdir.com/files/806357/content/doc021.png)
3.3.10 PROFIBUS DP (OPTION)
B
21
3 - Electrical Connections
DP
DN
DG
VP
1
2
3
4
• Galvanic isolation 500 Vac/1 min
• Compliance to the EIA RS485
standard for PROFIBUS DP;
• Connecting cable: twisted
pair cable as per PROFIBUS
specifications (e.g. Belden
B3079A);
• Max. lenght: 100 m at 12 Mb/s
Termination resistors 220
Ω and
390
Ω (
1
/
4
W, ±5%) for external
mounting on the first and end-
ing PROFIBUS stations only.
Detailed information concerning wiring and cables can be found on
the PROFIBUS Product Guide on Internet at:
http://www.profibus.com/online/list
DP
DN
DG
VP
Initial
PROFIBUS
station
DP
DN
DG
VP
Other
PROFIBUS
stations
DP
DN
DG
VP
Ending
PROFIBUS
station
220
Ω
390
Ω
390
Ω
220
Ω
390
Ω
390
Ω
33
4-40UNC-2B
5
9
6
1
To make the connections easier, a D-Sub type (9 poles)
connector, model AP-ADP-PRESA-DSUB/9P is provided
Must be used with a 9PIN male ERNI type part no. 103648 or sim-
ilar connector.
X5 D-SUB 9 poles
Signal
Description according to
PROFIBUS specifications
4
1
3
RxD/TxD-P (DP)
Receive data/transmission
data plus
6
2
8
RxD/TxD-N (DN)
Receive data/transmission
data negative
VP (VP)
3
5
DGND (DG)
Data transmission potential
(ground to 5V)
Supply voltage of the termi-
nating resistance-P, (P5V)
X5-SSI-uk 18-03-2009 17:53 Pagina 21