4 - Operation

TIMER COUNTING MODES

A - Counting start time inside the band,

end in control mode.

The time counting starts only when the error
is inside a ±1 digit band. The control action
is not affected by the Timer function.

C - Counting start time = timer launch

time, end in control mode.

The time counting starts when the timer is
launched. The control action is not affected
by the Timer function.

B - Counting start time inside the band,

end with control output forced to zero.

The time counting starts only when the error
is inside a ±1 digit band. At the end, the con-
trol output is forced to zero [1].

tdop

= 1

tdop

= 0

Timer start

counting

Time

elapsed

#tiMe

Timer
launch

Process
variable PV

Output OP [2]

OP3

±tbs

band

#t.Mod

= 2

Reset

±tbr band

SP

OP3

Timer start

counting

Time

elapsed

tdop

= 1

tdop

= 0

#tiMe

Timer
launch

Setpoint

OP3

#t.Mod

=3

Process
variable PV

Output OP [2]

±tbs

band

Reset

±tbr band

SP

OP3

OP = 0

tdop

= 1

tdop

= 0

#tiMe

Timer
launch

SP

Process
variable PV

Output OP [2]

#t.Mod

= 4

OP3

Reset

OP3

OP = 0

Notes
[1]
When the Timer is not running the control output is forced to zero.
[2] When the PID enable parameter is set to “0” (PID disabled) the OP output is set to “0”.