Space Ray RSTP Series User Manual
Page 21
Form 43206000
-20-
Sept 2011
Total Vent
Height
5 ft (152cm)
minimum
6 Diameter
Vent Connector
Total Vent
Height
1/4
(6mm)
per ft rise
Lateral
Single Heater Venting
Vent Cap
Flashing
2 (5cm)
Clearance
Thimble
Seal Joint
and Annular
Space
10 ft (305cm)
or less
2 ft (77cm)
minimum
2 ft (77cm) minimum
(when no wall or
parapet exists)
W
all or
Parapet
Vertical Through The Roof
SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)
SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)
SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)
SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)
When venting the heater horizontally through a combustible outside sidewall, the same requirements listed
previously for venting Vertical Through The Roof
Vertical Through The Roof
Vertical Through The Roof
Vertical Through The Roof apply except as follows:
1.
A vent passing through a combustible wall must pass through an approved clearance thimble (Air-Jet #4VT
or Ameri-Vent #4EWT or other thimbles) that are listed by a nationally recognized testing agency. Double-
wall Type B vent must be used for the portion of the vent system which passes through the combustible
sidewall.
2.
An approved vent cap (Breidert or equal) must be attached to the end of the vent pipe.
•
Minimum Equivalent Length = 5 ft. of pipe
•
Maximum Equivalent Length = 75 ft. of pipe
NOTE:
NOTE:
NOTE:
NOTE: To minimize problems associated with condensation in long horizontal runs, vent pipe can be insulated.
3.
When venting through a sidewall, the horizontal vent pipe shall rise not less than 1/4 inch per foot from the
start of the vent system to the vent terminal. All portions of the vent pipe shall be supported to prevent
sagging. (6’ spacing is recommended)
4.
A minimum clearance of 6 inches must be maintained between the outside wall and vent cap (18”
clearance will provide stability under high wind conditions).
5.
The horizontal venting system shall not terminate:
•
Less than 4 ft. (1.2m) below, 4 ft. (1.2m) horizontally from or 1 ft. (30cm) above any door, operable
window or gravity air inlet into any building. The bottom of the vent terminal shall be located at least 7 ft.
(2.1m) above grade or above snow accumulation level as determined by local codes.
•
Less than 3 ft. (0.9m) from a combustion air inlet.
•
Less than 3 ft. (0.9m) from any other building opening or any gas service regulator.
•
Less than 7 ft. (2.1m) above public walkways.
•
Directly over areas where condensate or vapor could create a nuisance or hazard or be harmful to the
operation of gas utility meters, regulators, relief valves, or other equipment. Building materials should
be protected from flue gases and condensate.
•
Less than 12” (0.30m) when directly below a combustible overhang.
6.
In regions of the country where prevailing winds are consistently higher than 40 mph, it may be necessary to
terminate the vent system above the roof level.
Sidewall Vent Cap
(Part No. 30297040)
2 (5cm)
Clearance
Thimble
No less than 1/4 (6mm)
rise per foot (0.3m) toward
vent terminal
6 (15cm)
minimum
Horizontal Through Sidewall