16

FirePLAce

inStALLAtiOn

Continued

CONNECTING FIREpLACE TO GAS
SUppLY

Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not

provided)

1. Route flexible gas line (provided by in-

staller) from equipment shutoff valve to
fireplace. Route flexible gas supply line
through one of the access holes on side
of fireplace.

2. Attach flexible gas line from gas supply to

control valve (see Figure 22).

3. Check all gas connections for leaks. See

Checking Gas Connections.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply

noncorrosive leak detection fluid

to all joints. Bubbles forming show

a leak. Correct all leaks at once.

pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace and its individual

equipment shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig (3.5 kPa) will damage fireplace
gas regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace or using
compressed air.

4. Check all joints of gas supply piping sys-

tem. Apply noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak. Correct all leaks at once.

5. Reconnect fireplace and equipment

shutoff valve to gas supply. Check recon-
nected fittings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see

Figure 23).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace or using
compressed air.

3. Check all joints from propane/LP supply

tank or gas meter to equipment shutoff
valve (see Figure 24 or Figure 25, page
17). Apply noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak.

4. Correct all leaks at once.

Figure 23 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

1/2" NPT
Incoming
Gas Line

Inlet
Pressure
Tap

Outlet
Pressure
Tap

Equipment
Shutoff
Valve

Flexible
Gas Line
Do NOT
Kink

Note: Wire Connections Not Shown for Clarity

Red Surface
Indicates For
Propane/LP Use
Only

Figure 22 - Connecting Flexible Gas Line

to Electronic Valve