SL Power Electronics GPMP600 User Manual
SL Power Electronics Equipment
CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
RA RATINGS:
Input: GPMP600: 100-240 V ac, 8.5 A, 50/60 Hz
GPMP700: 100-240 V ac, 9.5 A, 50/60 Hz
Outputs:
Output #1
Total
Model #
V
A
Watts
GPMP600-24-YYY
24
25/27 pk
600
GPMP600-28-YYY
28
21.5/23.5 pk
600
GPMP600-36-YYY
36
17/19 pk
600
GPMP700-48-YYY
48
14.6/15.6 pk
700
NOTES: 1. Maximum ambient temperature for rated output power is 50°C utilizing two integral 27 CFM Fans.
2. Maximum Operating Relative Humidity 96%, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before
application of power.
4. Peak current, 60 Sec with a 10% duty cycle
5. YYY indicates front cover colors and mounting options not related to safety.
CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of UL/CSA/EN/IEC
60601-1, 1
st
. Ed.
CLASSIFICATION:
(5.1) Protection against electric shock = Class I
(In accordance with sub-
clause 5 of EN 60601-1)
(5.2) Degree of protection against electric shock = Not acceptable for applied part without
additional isolation (contact factory for details)
(5.3) Protection against harmful ingress of water = Ordinary (no protection)
(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic mixture with
air, oxygen, or nitrous oxide. This evaluation is to be made on the end equipment by the OEM.
(5.6) Mode of operation = Continuous
GROUNDING: Protection Class I requires that at least one of the ground pins (Z28, D26) be bonded to Protective Earth in
the end application.
OUTPUTS: The outputs are not acceptable for patient connection without additional isolation.
OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some applications where an
overvoltage condition could result in a hazard as defined in applicable safety standards, redundant or additional overvoltage
protection may be required. Consult factory for details.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in the applicable safety
standards, must not be exceeded after installation to preserve the intended safety. The output power, ambient air temperature
and the availability, amount, direction and/or restriction of airflow influence the temperatures of these components.
FUSING: Fusing is provided only in the Input Line conductor of the power supply. Additional fusing, external to the power
supply must be provided to meet the requirements of the applicable standards.
WARNING! RISK OF FIRE!: A blown fuse is an indication of catastrophic failure of circuit component(s). Repair must
be performed by Condor authorized personnel.
41-35343-0002A 8/5/04
GPMP600/700 SERIES
INSTALLATION INSTRUCTIONS