SL Power Electronics GLD150 User Manual
Gld150 series installation instructions
a subsidiary of SL INDUSTRIES, INC.
ISO 9001 CERTIFIED
6050 King Street, Bldg A
Ventura, CA 93003
Phone: 805-486-4565
Fax: (805) 487-8911
MODEL NUMBERS: GLD150-X-C-YYY G, where X represents the output voltage which may be any number from 12
through 48. Suffix –C, when used, indicates optional cover is provided, and –YYY is any number 000 through 999 that
denotes value added options that do not effect safety and the G suffix denotes compliance with RoHS.
RATINGS:
Input: 100-240 V ac, 4.0 A, 50/60 Hz
Output:
180 W maximum with a minimum of 150 LFM, with or without cover.
150 W maximum with no airflow and no cover.
132 W maximum with no airflow and with cover.
Fan output is 12 V dc, 0.25 A
Notes: 1. Maximum ambient temperature for rated output power is 50°C.
2. Maximum Operating Relative Humidity 96%, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before
application of power.
CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of EN/IEC/UL 60601-1,
CSA 22.2 No. 601.1-M90.
CLASSIFICATION:
(5.1) Protection against electric shock = Class I
(In accordance with sub-
clause 5 of IEC 601-1)
(5.2) Degree of protection against electric shock = Not acceptable for applied part without
additional isolation (contact factory for details)
(5.3) Protection against harmful ingress of water = Ordinary (no protection)
(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic mixture with
air, oxygen, or nitrous oxide. This evaluation is to be made on the end equipment by the OEM.
(5.6) Mode of operation = Continuous
SAFETY DECLARATION: SL Power Electronics, Corp. declares under our sole
responsibility that all models listed above are in conformity with the applicable requirements
of EN60950 following the provisions of the Low Voltage Directive 73/23/EEC.
GROUNDING: Protection Class I requires that the ground terminal be bonded to Protective
Earth in the end application. Using this terminal for the primary system earthing terminal is not recommended.
OUTPUTS: It is recommended that the output common or return be connected to Protective Earth in the end
application. The output is not acceptable for patient connection without additional isolation. The DC output is
SELV under normal and single fault conditions.
OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some
applications where an overvoltage condition could result in a hazard as defined in applicable safety standards,
redundant or additional overvoltage protection may be required. Consult factory for details.
CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary circuits. The
components providing isolation from primary to secondary cannot be tested while installed in the power supply
without overstressing basic (primary to ground) insulation. All isolating components are individually 100 %
tested at 4800 V ac prior to installation.
41-34865-0001 Rev. E 12/14/06
Page 1 of 2
GLD150 SERIES
INSTALLATION INSTRUCTIONS