SL Power Electronics GPM80 User Manual
Page 2

41-32414-0001 Rev. E 11/13/06
OVERVOLTAGE PROTECTION: Only output #1 is monitored for an overvoltage condition. The trip-point
for a 5 volt output is 5.6 to 6.8 volts. In some applications where an overvoltage condition could result in a
hazard as defined in applicable safety standards, redundant or additional overvoltage protection may be required.
Consult factory for details.
CAUTION:
When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary circuits. The
components providing isolation from primary to secondary cannot be tested while installed in the power supply
without overstressing basic (primary to ground) insulation. All isolating components are individually 100 %
tested at 4800 V ac prior to installation.
ISOLATION:
The creepage distance between primary and ground is 4 mm minimum; between primary and
secondary circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled. The output
common is bypassed to ground using a 0.01 µF 1kV capacitor. The required creepage and clearance distances
from primary circuits to ground and secondary circuits must be maintained after installation to preserve the
intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in the
applicable safety standards, must not be exceeded after installation to preserve the intended safety. The output
power, ambient air temperature and the availability, amount, direction and/or restriction of airflow influence the
temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse is located in the phase lead only. EN 60601-1 requires
that both supply leads (phase and neutral) be protected against overcurrent. Complete overcurrent protection
must be provided in the host equipment. Fuse ratings must not exceed that specified for the internal fuse, must
meet the requirements of EN 60601-1 and be acceptable for the country in which the host equipment is to be
installed.
WARNING!
RISK OF FIRE!
A blown internal fuse is an indication of catastrophic failure of circuit
component(s). Repair must be performed by SL Power Electronics Corp. authorized personnel. Refer to fuse
marking on the supply for rating.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring traces
and heatsinks.
Attention, Consult
Accompanying Documents
Alternating Current
Attention, Dangerous Voltages
Protective Earth (Ground)
EXPLANATION OF SYMBOLS
C O N N E C T I O N S
J1 AC Input
J2 Multi-Output Models
J2 Single Output Models
Mating Connectors
1) Ground
1) Output 1 (+) 8) Output 2 (+) 1) Output 1 (+)
8) Common
J1 Amp Housing 640250-5
3) Neutral
2) Output 1 (+) 9) Output 2 (+) 2) Output 1 (+)
9) Common
J2 Amp Housing 1-640250-3
5) Line
3) Output 1 (+) 10) Power Fail
3) Output 1 (+) 10) Power Fail
Amp Contact 770476-1
4) Common
11) Output 3 (-) 4) Output 1 (+) 11) +Sense
CAUTION: Do not exceed
5) Common
12) Key
5) Common
12) Key
5 A per pin on J2.
6) Common
13) Output 4
6) Common
13) -Sense
7) Common
(+ or -)
7) Common
SL Power Electronics Corp. will not be liable for the safety, reliability or performance of these power supplies if a) any changes,
modifications or repairs are carried out by other than authorized agents of SL Power Electronics Corp., or b) the installation of the supply
is not in accordance with these installation instructions and the applicable UL, CSA, and/or IEC/EN safety standards
.