SL Power Electronics GPM40 User Manual
Page 2
OVERVOLTAGE PROTECTION: Only output #1 is monitored for an overvoltage condition. The
trip-point for a 5 volt output is 5.6 to 6.8 volts. In some applications where an overvoltage condition
could result in a hazard as defined in applicable safety standards, redundant or additional overvoltage
protection may be required. Consult factory for details.
ISOLATION: The components providing isolation from primary to secondary are 100 % tested at 4000
V ac. The creepage distance between primary and ground is 4 mm minimum; between primary and
secondary circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled. The
output common is bypassed to ground using a 0.01 µF 1 kV capacitor. The required creepage and
clearance distances from primary circuits to ground and secondary circuits must be maintained after
installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse is located in the phase lead only. EN 60601-1
requires that both supply leads (phase and neutral) be protected against overcurrent. Complete
overcurrent protection must be provided in the host equipment. Fuse ratings must not exceed that
specified for the internal fuse, must meet the requirements of EN 60601-1 and be acceptable for the
country in which the host equipment is to be installed.
WARNING! RISK OF FIRE! A blown internal fuse is an
indication of catastrophic failure of circuit component(s). Repair
must be performed by Condor authorized personnel. Refer to fuse
marking on the supply for rating.
WARNING! SHOCK HAZARD! Dangerous voltages are present
on some components, printed wiring traces and heatsinks.
C O N N E C T I O N S
Multi-Output Models
Single Output Models
J1 AC Input
J2 DC Outputs
J2 DC Output
J3
1) Line
1) Output 2 (+)
1) Output 1 (+)
1) + Sense
3) Neutral
2) Output 1 (+)
2) Output 1 (+)
2) Com Sense
CAUTION:
3) Output 1 (+)
3) Output 1 (+)
Do not exceed 5 A per contact on J2.
4) Common
4) Common
5) Common
5) Common
6) Output 3 (-)
6) Common
Mating Connectors:
Amp P/N 640250-3
Amp P/N 640250-6
Amp P/N 640250-6 Amp MTA100 Series
Contacts:
Amp P/N 770476-1
Amp P/N 770476-1
Amp P/N 770476-1
SL Power Electronics, Corp. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications
or repairs are carried out by other than authorized agents of SL Power Electronics, Corp., or b) the installation of the supply is not in
accordance with these installation instructions and the applicable UL, CSA, and/or IEC safety standards.
41-32580-0001 Rev. J 6/5/06
Page 2 of 2
Attention, Consult
Accompanying Documents
Alternating Current
Attention, Dangerous Voltages
Earth (Ground)
EXPLANATION OF SYMBOLS
Direct Current