ISOLATION: The creepage distance between primary and secondary circuits is 8 mm minimum. The
required creepage and clearance distances from primary circuits to secondary circuits must be
maintained after installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse for circuit protection is located in the phase lead
only. If a fuse is added to the neutral side or external dual fuses are provided, the fuse ratings must not
exceed that specified for the internal fuse, must meet the requirements of EN 60601-1, and be acceptable
for the country in which the host equipment is to be installed.
WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit
component(s). Refer to fuse marking on the supply for rating. Repair must be performed by Condor
authorized personnel.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring
traces and heatsinks.
Attention, Consult
Accom panying Docum ents
Alternating Current
Attention, Dangerous Voltages
EXPLANATIO N O F SYM BO LS
Direct Current
C O N N E C T I O N S
J1 Pin
AC Input
J2 Pin
DC Output
MATING CONNECTORS
1
Line
1
Output (+)
J1
Amp Housing 640250-3 Contact 770476-1
3
Neutral
2
Output (+)
J2
Amp Housing 640250-6 Contact 770476-1
3
Output (+)
J3
Amp MTA-100 Receptacle
J3 Pin
4
Return
1
+ Sense
5
Return
CAUTION: Do not exceed 5 A per pin on J2.
2
- Sense
6
Return
SL Power Electronics, Corp. Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are carried out by other
than authorized agents of SL Power Electronics Corp., or b) the installation of the supply is not in accordance with these installation instructions and the applicable UL, CSA, and
EN/IEC safety standards.
41-35405-0001 Rev. C 6/8/06
Page 2 of 2
- GPC55 GPC40 GECA20 GLC65 Single GLC65 Triple Output GLM65 Triple Output GEM600 GEM750 GLD140 GLD150 GPFC110 GLM75 Single Output GLM50 Triple O/P MINT1022 MINT1110 GPFM250 GPMP600 GPMP700 GSM28 GSM15 G2T60 GPC200 GPC130 GPC140 GLC75 Multiple Output GNT400 GNT30 GLC50 Single GLC50 Triple GPFM115 GPFM600 GPM55 GSM11