beautypg.com

Sensoray 2518 User Manual

Page 13

background image

Sensoray Model 2518/2519 Ethernet Smart A/D™

10

Configuration

Figure 9: Model 518 programming shunts

4.3.2 Base Address Selection

IRQ and I/O addresses are factory programmed and
should never need to be changed. When installed on a
model 2509 Ethernet base board, model 518 daughter
boards should be configured as follows:

Address (E1 to E8). The lower model 518 board,
which is the only model 518 board residing on model
2518, is set to base address 2B0 hex. In the case of
model 2519 only, the upper model 518 board is set to
base address 2B4 hex.

Interrupts (IRQ2 to IRQ7). The lower model 518
board is set to generate interrupts on IRQ2, and on
model 2519 only, the upper model 518 board is set to
generate interrupts on IRQ3.

See the model 518 instruction manual for details on how
to configure model 518 interrupt and address options.

4.3.3 Signal Conditioning Circuits

Each of the eight sensor channels on a model 518 Smart
A/D™ board is provided with a signal conditioning
circuit (SCC) which may be inserted into the sense signal
path. This conditioning circuit performs three functions:

q

Common-mode tie-down. This function helps to
prevent the common mode voltage (CMV) from
straying beyond the input CMV range of the Smart
A/D™ measurement section. This function is
required when a sensor channel is driven from an
isolated source, such as a battery, isolated power
supply, or thermocouple.

q

Open-sensor detect. If either of the two sense
signals should become disconnected from the source,
this function forces a differential voltage of 700mV,
minimum, to appear across the sense inputs. This

function is useful when a sensor is used in a control
loop.

q

RF shunt. This function, which shunts RF noise to
ground, is essential when connecting to isolated
sources, such as thermocouples.

4.3.4 Side Effects

The input impedance of a channel’s Sense inputs is
reduced when that channel’s SCC is enabled. See
“General Specifications” on page 26 for details.

Ordinarily, this reduction of input impedance will not be
an issue for thermocouples. In the case of other types of
voltage sources, however, measurement accuracy may be
degraded if such sources have high source impedance.

4.3.5 Recommended Settings

The decision of whether or not to enable a channel SCC
is influenced primarily by the type of sensor to be
interfaced, and, in the case of active sources, whether or
not the source is ground-referenced.

Listed below are recommendations for enabling vs.
disabling the SCC:

4.3.6 Shunt Mapping

Shunts E9 through E24 are used to control the enabling
of SCCs for all sensor channels. Each channel is
affiliated with two shunts. To enable a channel’s SCC,
you must install both of the affiliated shunts. Similarly,
to disable the SCC, you must remove both shunts.

E

1

E

2

E

3

E

4

E

5

E

6

E

7

E

8

IR

Q

2

IR

Q

7

IR

Q

6

IR

Q

5

IR

Q

4

IR

Q

3

E19
E20

E17
E18

E23
E24

E21
E22

E11
E12

E9
E10

E15
E16

E13
E14

Table 3: Recommended signal conditioner settings

Sensor Type

SCC

Ungrounded Thermocouple

Enabled

Isolated DC Voltage Source

Grounded Thermocouple

Disabled

Ground-referenced DC Voltage Source

4-to-20 mA loop

Resistor

RTD

Strain/Pressure Gage

Thermistor

This manual is related to the following products: