beautypg.com

Seaward 50 PrimeTest User Manual

Page 16

background image

PrimeTest 50

Operating Instructions

14

4 Specification

Earth Continuity

Pass Limit

0.2:

Accuracy* ±

0.03:

Test current 200mA minimum
Test voltage 9V nominal

Insulation resistance

Pass Limit

1.0M: CLI, 2.0M: CL II

2.0M: Mains cord
Accuracy ±

0.1M:

Test voltage 500V
Test current >1mA into 500k:
Test current <2mA into 2k:

Cord Test

Earth continuity, insulation resistance as above.

Check for Live and Neutral open circuit, short
circuit or reversed polarity.

*

When used with Seaward test lead, Part Number 347A002

Environmental rating

IP40
Operating temperature range 0°C to 40°C, without
moisture condensation.
Storage temperature range –25° to 65°. Batteries
should be removed prior to storage.
Overvoltage category 300V CAT II

5 Maintenance

Clean only with a dry cloth; do not use solvents.
Before use, ensure unit is clean and dry; visually
inspect all leads, connectors, and case. Any damage
or wear must be rectified to preserve user safety.

Check the battery contacts and compartment are
free of electrolytic contamination.
Any contamination of the battery contacts or
compartment should be cleaned with a dry cloth.