Service Diagnosis: Diagnostic Light Analysis

CME1356R and CME1656R

May 2001

Page 31

Problem or Symptom

Possible Cause

Probable Correction

Machine is off

Bin is full

Use some ice

Bin thermostat is closed

Check thermostat

Power is off, check
Lights.

If all Lights are out, check power supply,
restore power if off

Transformer is open

If all Lights are out and there is power, check
transformer output for 24 vac

Unit has been switched
off or has finished a
Clean cycle, Off Light is
glowing

Push and release Freeze button

Unit has Shut Down

Check for Refrigeration or Water Error

Unit is off on a Water
Error

Water supply inadequate

Check water Light, if the Light blinks 2 times
and repeats, check the water inlet valve for
proper water flow.**

Water pump malfunction

Check that pump hose is attached and if
pump is plugged in and working.

Water level sensor may
have failed.

Check float stem, reset machine. If it will not
reset or gives another water error and
everything else is OK, replace the water level
sensor.

Unit is off on a
Refrigeration Error

Low discharge or long
freeze cycle

Check refrigeration Light. If the Light is
glowing, there is a probable refrigeration
problem - fan motor could have failed.

Harvest problem

Check refrigeration Light. If the Light blinks
once and repeats, look for a harvest problem.
where some cubes were sensed.**

Check refrigeration Light. If the Light blinks
two times and repeats, look for a harvest
problem. - no cubes sensed**

High Discharge Temp

Check refrigeration Light. If the Light blinks 3
times and then repeats, check for a reason for
high discharge temperatures - fan motor hot
ambient.

Unit does not go into
harvest - exceeds
maximum freeze time

Push and release Off button. Push and
release Freeze button. Check operation.

Push cube size float down and check
operation.

Exceeds maximum
harvest time

Check for cause of long harvest cycle**

Unit runs and both
Diagnostic lites are ON

Temperature sensors out
of range

Replace the temperature sensor set (water
and discharge).

Same, only 1 light on

Reservoir temp. wrong

Check water temp. and sensor.

* Machine may be reset by pushing and releasing the Off button, then pushing and releasing the