beautypg.com

Remote condenser location – Scotsman CME1356R User Manual

Page 11

background image

Remote Condenser Location

Use the following for planning the placement of

the condenser relative to the ice machine

Location Limits - condenser location must not

exceed ANY of the following limits:

Maximum rise from the ice machine to the
condenser is 35 physical feet

Maximum drop from the ice machine to the
condenser is 15 physical feet

Physical line set maximum length is 100 feet.

Calculated line set length maximum is 150.

Calculation Formula:

Drop = dd x 6.6 (dd = distance in feet)

Rise = rd x 1.7 (rd = distance in feet)

Horizontal Run = hd x 1 (hd = distance in
feet)

Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these

requirements must receive prior written

authorization from Scotsman.

Do NOT:

Route a line set that rises, then falls, then
rises.

Route a line set that falls, then rises, then
falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice

machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would

be acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and

then 100 feet away horizontally.

35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is

greater than the 150 maximum and is NOT

acceptable.

Operating a machine with an unacceptable

configuration will void the refrigeration system

warranty.

22

.87"

17

.15"

40.35"

hd

rd

dd

Remote

Condenser

Located ABOVE

Ice Machine

Remote

Condenser

Located BELOW

Ice Machine

Condenser Distance &

Location Schematic

Max 35’

Max 15’

CME1356R and CME1656R

May 2001

Page 11

This manual is related to the following products: