Remote Condenser Location

Use the following for planning the placement of the

condenser relative to the ice machine

Location Limits - condenser location must not exceed

ANY of the following limits:

• Maximum rise from the ice machine to the

condenser is 35 physical feet

• Maximum drop from the ice machine to the

condenser is 15 physical feet

• Physical line set maximum length is 100 feet.

• Calculated line set length maximum is 150.

Calculation Formula:

• Drop = dd x 6.6 (dd = distance in feet)

• Rise = rd x 1.7 (rd = distance in feet)

• Horizontal Run = hd x 1 (hd = distance in feet)

• Calculation: Drop(s) + Rise(s) + Horizontal

Run = dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these requirements

must receive prior written authorization from

Scotsman.

Do NOT:

• Route a line set that rises, then falls, then rises.

• Route a line set that falls, then rises, then falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice

machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would be

acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and

then 100 feet away horizontally. 35 x 1.7 = 59.5.

59.5 +100 = 159.5. 159.5 is greater than the 150

maximum and is NOT acceptable.

22

.8

7"

17

.1

5"

40.35"

dd

hd

rd

Remote Condenser Located

ABOVE Ice Machine

Remote Condenser Located

BELOW Ice Machine

Max 35’

Max 15’

Condenser Distance &

Location Schematic