EH330, EH430 D and ECC Condensing Unit

Remote Low Side Cuber User Manual

October 2014

Page 8

Create the System

Plan the installation. The system consists of three

parts: the ice making head, the condensing unit and

the interconnecting tubing. Of these, the biggest

variable is the interconnecting tubing.

Tubing: The tubing consists of three insulated and

sealed soft copper tubes. One tube, the liquid line,

is 3/8” OD. The vapor tube is ½” OD and the suction

tube is ¾” OD. A site inspection will determine what

length of tubing is required for the installation.

In 2013 Scotsman made a change to the Eclipse

tubing kits:
• Prior Tubing Kits: They each contain a small

holding charge of R-404A and have quick

connects at the ends.

• Current Tubing Kits: The do not contain any

refrigerant and do not have quick connects.

Either type can be used to connect the head and

condensing unit.
Quick Connect type: Check ice making head and

condensing unit for quick connects. If none, recover

refrigerant from tubing and cut the quick connects off.

If the head or condensing unit has a quick connect,

recover refrigerant and only cut off the quick connect

at the system with the stub connections.

Tubing without quick connects: Check head and

condensing unit, if neither have quick connects, use

as is. If one or both do, obtain kit KTE6 to add quick

connects to the line set.

Excess tubing must be shortened at the job site.

Installations with greater than 20 feet of vertical lift

between ice machine and the compressor require

a suction line trap. The suction line requires careful

handling and large radius bends to prevent kinking.

Roof mounting: Some installations will require the use

of a hoist to lift the components to the roof.

Pad mounting: The condensing unit may be located

below the ice making section, up to a limit of 15 feet.

Distance from unit: Limited to the length of the

available tubing.

Elevation: Condensing unit limited to 35 feet above

the ice making head.

Condensing Unit: Electrical power must be supplied to

the condensing unit, it will be separate from the head.

The remote tubing connections are at the top of the

machine, and connections should not be made until

the machine is nearly in its final installed position.

The 115/60 Hz ice making section is cord connected

and requires an outlet within 6 feet of the installation.

Interconnecting wires: A low voltage interconnecting

wire harness is included with the condensing unit.

One end plugs into the ice making head and the other

into the condensing unit. The system will NOT operate

without this harness.

Exposed tubing: Minimize the amount of tubing

exposed outdoors.