Scotsman EH330 D with ECC Condensing Unit User Manual

Page 21

background image

EH330, EH430 D and ECC Condensing Unit

Remote Low Side Cuber User Manual

October 2014

Page 20

Scotsman offers Stera Sheen Green Label

sanitizer, part number 14-0382-01.

15. Thoroughly wash all surfaces of the ice thickness

sensor, water level sensor, curtain and water

distributor with the sanitizer solution.

16. Wash all interior surfaces of the freezing

compartment, including evaporator cover and right

side panel liner with the sanitizer solution.

17. Return water level sensor, ice thickness sensor,

water distributor and curtain to their normal

positions. Be sure water level sensor and ice

thickness sensor are completely dry.

18. Push and release the Clean button. The yellow

Clean light will blink and the display will show C.

The machine will go through a harvest cycle, drain

the reservoir and begin to refill it.

19. Observe code display, when it blinks the

characters “Ad1” immediately go to the next step.

20. Pour the sanitizing solution into the reservoir until

it is full. The unit will circulate the sanitizer, then

drain and flush it. This will take 35 minutes, then

the machine will stop and the display will show O.

21. Return all panels and covers removed to their

original positions.

22. Push and release the On button to resume ice

making.

Other Maintenance
The remote air cooled condenser coil must be

cleaned occasionally to keep the system operating at

high efficiency. Airflow is from the outside in.

Remove any large debris from the outside of the coil.

Vacuum accumulated dust.

Wash out the coils with water.

Caution: Do NOT use excessive water pressure as

that will bend the fins.

If the coils have become coated with grease, a coil

cleaner will have to be used to wash the coils.

Disconnect power to the condensing unit and remove

the condenser top.

Inspect the fan blade to be sure it is not cracked and

is clean.

Return the condenser top to its original position and

reconnect the power supply.

Step 13.

Release

probes by

pushing in on

white buttons

and pulling

probe down

out of holder.

Rotating fan blade can

cause personal injury.
Disconnect power to

unit before servicing it.