Initial Start Up

Pre Start

A soak-out period of four hours is optional for this

system. If desired, powering the compressor unit

for four hours prior to start up allows the crankcase

heater to warm up the oil in the compressor.

Start Up
1. Connect power to the condensing unit and move

its toggle switch to Run or On.

2. Open the water supply valve.

3. Remove the head’s front panel. Check for any

packing or wires rubbing moving parts. Note

location of control board in upper left corner of the

machine’s front.

4. Remove any tape securing curtain to evaporator.

5. Switch on the electrical power to the EH head.

Observe that some of the control’s indicator lights

glow and its display shows O.

6. Push and release the ON button. The code display

will begin to blink F.

The purge valve opens, the water pump starts and the

inlet water valve opens to add water to the reservoir.

In a few seconds the purge valve closes and the

water pump stops. Water will flow into the machine

until the reservoir is full. The vapor valves and harvest

assist devices will activate, then the compressor and

water pump will start. The F will be on steady.

Note: Because the condensing unit is external to the

ice making section, no visible signs of operation will

be noticeable until the water begins to cool and frost

forms on the evaporator tubing.

7. Go to the condensing unit and confirm that the

compressor and fan motor are operating. Warm

air will be discharged from the condenser.

Observe the Ready for Harvest indicator light. It may

blink early in the cycle, that is normal. The control will

ignore that signal for the first 6 minutes of freeze.

During the Freeze cycle move the curtains and

observe that the SW1 or SW2 light on the control

board blinks On when the curtain moves away from

the evaporator and Off when returned to its normal

position.

Note: Moving a curtain during the Freeze cycle has no

affect on control function, but will cause water to flow

into the cube chute. When enough ice has frozen, the

Ready for Harvest indicator light will be on steady.

After it’s been on steady for a few seconds Harvest

will begin.

The display shows an H. The vapor valve in the EH

opens, and the harvest assist mechanism activates.

In the CU the condenser bypass valve opens and

the receiver inlet valve closes. In the EH, the purge

valve opens to drain some water, when it does the

inlet water valve opens to refill the reservoir. After a

few seconds the purge valve closes but the inlet water

valve continues to fill the reservoir. Harvest continues

until the ice is released as a unit and forces the

curtain to open.

When the curtain opens it signals the controller that

harvest is complete, and it returns the unit to a freeze

cycle.

8. Check the ice harvested for proper bridge

thickness. The ice bridge is factory set at 1/8 inch.

If needed, adjust bridge thickness. Do NOT make

it too thin.

9. Return the front panel to its normal position and

secure it to the machine.

10. Instruct the user in the operation of the machine

and its maintenance requirements.

11. Fill out and mail the warranty registration form or

register it on line at www.scotsman-ice.com.