EH330, EH430 D and ECC Condensing Unit

Remote Low Side Cuber User Manual

October 2014

Page 22

Operational Characteristics 1800 lb system

Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.

70/70/50

90/90/70

120/110/100

Freeze

10 to 14 minutes

12 to 16 minutes

17 to 19 minutes

Harvest

1 to 1.5 minutes

1 to 1.5 minutes

.5 to 1 minute

System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F

70/70/50

90/90/70

120/110/100

Suction at head, end of Freeze 25 to 35 PSIG

25 to 35 PSIG

25 to 35 PSIG

Suction at head, Harvest - Peak 80 to 100 PSIG

90 to 110 PSIG

140 t0 160 PSIG

Discharge at Condensing Unit:

Freeze - 5 minutes in

260 to 280 PSIG

260 to 280 PSIG

330 to 350 PSIG

Headmaster maintains a minimum discharge pressure during freeze of 217 PSIG + 25, -15 PSIG.

CPR Valve Setting: 55 - 60 PSIG.

Note: CPR allows a maximum low side pressure at the compressor. Maximum only occurs during harvest.

Refrigerant Charge
• 1800 - 232 oz
Compressor Amps, 1800
• Three Phase - 10 to 14
Batch Weight: 13 to 14 lb

Discharge Pressure Cut Out Switch
• Cuts Out at: 450 PSIG Resets at: 350 PSIG