Modbus Remote I/O Communication Module RTU-485

DVP-PLC Application Manual

5

2.4 Address

Switch

The switch is used on setting up the communication address of RTU-485. Range: H’01 ~ H’F0 (decimal: 1 ~

240)

Switch setting

Content

H’01 ~ H’F0

Valid communication address

ID0 ~ ID7 are defined as: 2

0

, 2

1

, 2

2

, …2

6

, 2

7

H’00,

H’F1 ~ H’FF

Invalid communication address

Example: If you need to set the address of RTU-485 to 26, swich the DIP switch corresponding to ID4 to “ON”,

switch corresponding to ID3 to “ON” and switch corresponding to ID1 to “ON”.

Note:

z Please set up the address when the power of RTU-485 is switched off. After the setup is completed, re-power

RTU-485.

z When RTU-485 is operating, changing the setting of communication address will be invalid.

z Use slotted screwdriver to adjust the switch carefully in case you scratch the switch.

2.5

Communication Mode Switch

These switches are for:

z Setting up communication format (PA0 ~ PA3, A/R)

z Setting up baud rate (DR0 ~ DR2)

PA3

PA2

PA1

PA0

A/R

Format

OFF OFF OFF OFF ON

7,E,1,

ASCII

OFF OFF OFF ON ON

7,O,1,

ASCII

OFF OFF ON OFF ON

7,E,2,

ASCII

OFF OFF ON ON ON

7,O,2,

ASCII

OFF ON OFF OFF ON

7,N,2,

ASCII

OFF ON OFF ON ON

8,E,1,

ASCII

OFF ON ON OFF ON

8,O,1,

ASCII

OFF ON ON ON ON

8,N,1,

ASCII

PA3

PA2

PA1

PA0

A/R

Format

ON OFF OFF OFF ON

8,N,2,

ASCII

OFF ON OFF ON OFF

8,E,1,

RTU

OFF ON ON OFF OFF

8,O,1,

RTU

OFF ON ON ON OFF

8,N,1,

RTU

ON OFF OFF OFF OFF

8,N,2,

RTU

DR2

DR1

DR0

Baud rate (bps)

OFF OFF OFF

1,200

OFF OFF ON

2,400

OFF ON OFF

4,800

OFF ON ON

9,600

ON OFF OFF

19,200