Modbus Remote I/O Communication Module RTU-485
DVP-PLC Application Manual
8
Communication
address
Attribute
Content
Explanation
H’001C R
Model code of the 5
th
special module
The model code of the 5
th
special module
connected to RTU-485.
H’001D R
Model code of the 6
th
special module
The model code of the 6
th
special module
connected to RTU-485.
H’001E R
Model code of the 7
th
special module
The model code of the 7
th
special module
connected to RTU-485.
H’001F R
Model code of the 8
th
special module
The model code of the 8
th
special module
connected to RTU-485.
4.4 Error
Codes
Code
Indication
Explanation
0001
Incorrect function code
RTU-485 does not support this function code.
0002
Incorrect operand address
The address of a certain device is not within the
range, orthe data written into it are incorrect.
0003
Incorrect data
The data read/written exceed the maximum length.
0004
RTU-485 STOP
RTU-485 in STOP mode.
000B
Incorrect communication format
The length of data received by RTU-485 is too short.
000C
Incorrect communication format
The length of data received by RTU-485 is too long.
5
Function Codes RTU-485 Supports
RTU-485 complies with the standard Modbus protocol, supporting 7 function codes, which are H’01, H’02, H’03,
H’05, H’06, H’0F and H’10. Please refer to the standard Modbus protocol for the specific data format of each
function code.
Code
Function
Data type
Applicable address
H’01
Reading the output status of bit
device.
bit
DO area: H’0500 ~ H’057F
H’02
Reading the input status of bit
device
word bit
DI area: H’0400 ~ H’047F
Area for special functions: H’0000 ~ H’001F
CR for the 1
st
special module: H’1600 ~ H’1630
CR for the 2
nd
special module: H’1640 ~ H’1670
CR for the 3
rd
special module: H’1680 ~ H’16B0
CR for the 4
th
special module: H’16C0 ~ H’16F0
CR for the 5
th
special module: H’1700 ~ H’1730
CR for the 6
th
special module: H’1740 ~ H’1670
CR for the 7
th
special module: H’1780 ~ H’16B0
H’03 Reading
register
bit
CR for the 8
th
special module: H’17C0 ~ H’17F0
H’05
Writing single datum into bit
device
bit
DO area: H’0500 ~ H’057F
RTU-485 RUN/STOP mode: H’0003
H’06
Writing single datum into register
word
Applicable to CR with R/W attribute in the 1
st
~ 8
th
special module
H’0F
DO area: H’0500 ~ H’057F
H’10
Writing many data into bit device
bit
Applicable to CR with R/W attribute in the 1
st
~ 8
th
special module