Satel ETHM-1 User Manual
Page 5
![background image](https://www.manualsdir.com/files/803276/content/doc005.png)
SATEL 2014-04-02
Answers description:
RTC and basic status bits
- 7 bytes - time: YYYY-MM-DD hh:mm:ss - 0xYY, 0xYY, 0xMM, 0xDD, 0xhh, 0xmm, 0xss
1 byte - .210 - day of the week (0 = Monday, 1 = Tuesday, ..., 6 = Sunday)
.7 - 1 = service mode
.6 - 1 = troubles in the system (= flashing TROUBLE LED in keypad)
1 byte -
.7 - 1 = ACU-100 are present in the system
.6 - 1 = INT-RX are present in the system
.5 - 1 = troubles memory is set in INTEGRA panel
.4 - 1 = Grade2/Grade3 option is set in INTEGRA panel
.3210 - INTEGRA type:
0 = INTEGRA 24
1 = INTEGRA 32
2 = INTEGRA 64 / INTEGRA 64 PLUS
3 = INTEGRA 128 / INTEGRA 128 PLUS
4 = INTEGRA 128-WRL
8 = INTEGRA 256 PLUS
(to read detailed type use 0x7E command)
troubles part 1
- 16 bytes
- troubles - technical zones
8 bytes
- expanders AC trouble
8 bytes
- expanders BATT trouble
8 bytes
- expanders NO BATT trouble
3 bytes
- system troubles (see description below)
1 byte
- CA-64 PTSA modules AC trouble
1 byte
- CA-64 PTSA modules BATT trouble
1 byte
- CA-64 PTSA modules NO BATT trouble
1 byte
- ETHM-1 monitoring trouble
troubles part 2
- 8 bytes
- proximity card readers head A trouble
8 bytes
- proximity card readers head B trouble
8 bytes
- expanders supply output overload
2 bytes
- addressable zone expanders short circuit or jammed ACU-100 modules
troubles part 3
- 15 bytes
- ACU-100 modules jam level
15 bytes
- radio devices with low battery
15 bytes
- radio devices with no communication
15 bytes
- radio outputs with no communication
troubles part 4
- 8 bytes
- expanders with no communication
8 bytes
- switcherooed expanders
1 byte
- LCD keypads with no communication
1 byte
- switcherooed LCD keypads
1 byte
- ETHM-1 modules with no LAN cable / INT-RS modules with no DSR signal
8 bytes
- expanders tamper
1 byte
- LCD keypads tamper
1 byte
- LCD keypad initiation errors
1 byte
- auxiliary STM troubles (in INTEGRA PLUS, in others value of this field is 0)
troubles part 5
- 1 byte
- low battery in masters key fobs
30 bytes
- low battery in users key fobs
troubles part 6
-
15 bytes
- radio devices with low battery (last 120 ACU-100 devices in INTEGRA 256 PLUS)
15 bytes
- radio devices with no communication (last 120 ACU-100 devices in INTEGRA 256 PLUS)
15 bytes
- radio outputs with no communication (last 120 ACU-100 devices in INTEGRA 256 PLUS)
troubles part 7
- 16 bytes
- troubles - technical zones 129..256 in INTEGRA 256 PLUS
16 bytes
- memory of troubles - technical zones 129..256 in INTEGRA 256 PLUS
15 bytes
- ACU-100 modules jam level (last 15 ACU-100 modules in INTEGRA 256 PLUS)
- 5 -