Appendix c: technical specifications – RLE LDZ4 User Manual

Page 17

background image

User Guide: LDZ4

Appendix C: Technical Specifications

www.rletech.com 970.484.6510

11

APPENDIX C: TECHNICAL SPECIFICATIONS

Power

24VAC/VDC (±10%) @ 300mA max.

Inputs

Water Leak Detection Cable Supplied with 15’ (4.57m) leader cable per zone

Maximum

Length

1000’ (305m)/zone

Detection Response Time

<20sec

Outputs

Relay

1 Form C Leak Relay, 1 Form C Cable Fault Relay, 1 From C Summary Alarm
Relay (silenceable); 1A @ 24VDC, 0.5A resistive @ 120VAC; configurable
for supervised or non-supervised, latched or non-latched

Alarm Notification

Audible

Alarm

85DBA @ 2’ (0.6m),
re-sound 0-24hrs

Front Panel Interface

LED

Indicators

1 green Power (on/off); 4 amber Cable Fault; 4 red Leak Detected (1 per
zone)

Push

Buttons

1 Reset, 1 Quiet & 1 Test

Operating Environment

Temperature
Humidity
Altitude


32° to 122°F (0° to 50°C)
5% to 95% RH, non-condensing
10,000’ (3,048m) max.

Storage Environment

-4° to 158°F (-20° to 70°C)

Dimensions

10.5”W x 8.0”H x 2.0”D
(267mmW x 203mmH x 51mmD)

Weight

4 lbs. (1.82kg)

Mounting

Vertical wall mount

Certifications

UL508A/CUL508A, FCC Part 15