beautypg.com

P1 - power, Tb3 - leak relay, Tb2 - cable fault relay – RLE LDZ4 User Manual

Page 10: Tb1 - summary relay, Sw1 - relays and alarm, Sw1, position 1, Sw1, position 2

background image

Chapter 2: Connections & Settings

User Guide: LDZ4

4 970.484.6510

www.rletech.com

2-1.2 P1 - Power

Power can also be supplied to the unit through P1. This is a wall adapter plug connection.

2-1.3 TB3 - Leak Relay

This is the Leak Relay output terminal block (Form C). A status LED is located above the relay, which
will indicate the state of the relay (on/off). This relay can be configured as supervised or unsupervised,
latched or unlatched. Connect the Leak Relay wires to TB3 as follows:

TB3-1 Leak alarm normally open (NO)
TB3-2 Leak alarm common (C)
TB3-3 Leak alarm normally closed (NC)

2-1.4 TB2 - Cable Fault Relay

This is the Cable Fault Relay output terminal block (Form C). A status LED is located above the relay,
which will indicate the state of the relay (on/off). This relay can be configured as supervised or
unsupervised, latched or unlatched. Connect the Leak Relay wires to TB2 as follows:

TB2-1 Cable fault alarm normally open (NO)
TB2-2 Cable fault alarm common (C)
TB2-3 Cable fault alarm normally closed (NC)

2-1.5 TB1 - Summary Relay

This is the Summary Relay output terminal block (Form C). A status LED is located above the relay,
which will indicate the state of the relay (on/off). This relay can be configured as supervised or
unsupervised, latched or unlatched. Connect the Leak Relay wires to TB1 as follows:

TB1-1 Summary alarm normally open (NO)
TB1-2 Summary alarm common (C)
TB1-3 Summary alarm normally closed (NC)

2-1.6 TB7 through TB4 - Zone 1 through Zone 4 Leak Detection Cable Inputs.

Leak detection cables connect to TB7-TB4 (zones 1-4). A fifteen foot leader cable is provided to connect
the LDZ4 to the Leak Detection Cable(s). Connect the leader cable wires as follows:

(x=7....4)

TBx-1 White wire

TBx-2

Black

wire

TBx-3 Green wire

TBx-4

Red

wire

2-2

SW1 - RELAYS AND ALARM

2-2.1 SW1, Position 1

Configures the relays as supervised or non-supervised. If a relay is supervised, the
relay picks until power goes off or until an alarm is detected. The alarm then
releases to announce a change in state. A non-supervised relay releases only when
an alarm is detected.

1

=

Supervised

0 = Non-supervised (factory default)

2-2.2 SW1, Position 2

Configures the relays as latched or non-latched. If a relay is latched, the relay will
remain in an alarm condition until the Reset switch is pressed. If a relay is non-
latched, the relay will remain in alarm until either the Reset switch is pressed, or the

For all SW Settings:

1 – Switch is on.

0 – Switch is off.